Products
Vertical Condensate Coolers

VCC Vertical Condensate Coolers

The VCC Series are installed to reduce condensate temperature to acceptable limits when the condensate is to be discharged to drain. Cooling water is connected to the inlet of the included temperature regulating valve to maintain the desired condensate outlet temperature. All units are vented to atmosphere to ensure any flash steam is properly relieved. A steam trap is included on the drain to eliminate the possibility of steam discharge.

How To Size/Order

Use the Capacity Table to determine the proper tank diameter based on the incoming Condensate Load in lbs/hr. See note regarding base conditions for Condensate and Cooling Water temperatures. Consult factory for sizing with alternate conditions.

Example: 
Condensate Load: 8,000 lbs/hr
Condensate Temperature Incoming: 210ºF
Condensate Temperature Leaving: 140ºF
Cooling Water Temp: 60ºF

Based on 8000 lbs/hr at standard conditions 
Therefore Choose: 16” Condensate Cooler
Model Code: VCC-16-22-F150

The VCC Series are installed to reduce condensate temperature to acceptable limits when the condensate is to be discharged to drain. Cooling water is connected to the inlet of the included temperature regulating valve to maintain the desired condensate outlet temperature.

ModelTank Dia.SizeType Max PMO (psig)Capacity (lb/h)Total Load (lbs/hr)
VCC-6-18-F1506"2 1/2"150# FLG1502,063
VCC-8-20-F1508"4"150# FLG1504,000
VCC-12-21-F15012"5"150# FLG1509,000
VCC-16-22-F15016"6"150# FLG15019,700
Product Overview
The VCC Series are installed to reduce condensate temperature to acceptable limits when the condensate is to be discharged to drain. Cooling water is connected to the inlet of the included temperature regulating valve to maintain the desired condensate outlet temperature. All units are vented to atmosphere to ensure any flash steam is properly relieved. A steam trap is included on the drain to eliminate the possibility of steam discharge.
Dimensions and Weights

Selection / Sizing / Capacities

Use the Capacity Table to determine the proper tank diameter based on the incoming Condensate Load in lbs/hr. See note regarding base conditions for Condensate and Cooling Water temperatures. Consult factory for sizing with alternate conditions.

Example: 
Condensate Load: 8,000 lbs/hr
Condensate Temperature Incoming: 210ºF
Condensate Temperature Leaving: 140ºF
Cooling Water Temp: 60ºF

Based on 8000 lbs/hr at standard conditions 
Therefore Choose: 16” Condensate Cooler
Model Code: VCC-16-22-F150