From the Capacity chart, find the inlet pressure and required regulator outlet pressure. Follow across chart to nearest capacity (steam) that meets or slightly exceeds demand requirements. Follow vertically up to determine appropriate size. When exact application values are not shown, interpolate between values. From the spring range chart, select the spring range that accommodates the required outlet set pressure.
455 Spring Selection Table:
Example:
Application: 1000 lbs/hr of 20 PSIG Steam reduced to 5 PSIG
Model Code: 455-16-N-65 (455-Series, 11/2” NPT, 1-6 PSIG spring range)