Filter By
Close X
Capillary Length

Temperature Range





Special Options
Close X

Steam Inlet Pressure Range (Low)
Low Pressure - PT Pilot (pressure under 15 PSIG) is used with HD-LP Low-PRessure main valve

Filter
PTU

PTU Temperature Pilot

Copper sensing bulb with Union connection allowing it to be screwed into the side of a tank or pipe. The sensing bulb is in direct contact with the process fluid. Sensing bulb can be removed by unscrewing union nut (union hub remains in place).

ModelSensing BulbTemperature RangeCapillary LengthWeight (lbs)
PTU-12-8Copper Bulb w/ Union60 - 120°F8 Feet8
PTU-14-8Copper Bulb w/ Union100 - 160°F8 Feet8
PTU-29-8Copper Bulb w/ Union120 - 180°F8 Feet8
PTU-30-8Copper Bulb w/ Union160 - 220°F8 Feet8
PTU-32-8Copper Bulb w/ Union240 - 300°F8 Feet8
PTU-12-15Copper Bulb w/ Union60 - 120°F15 Feet8
PTU-31-15Copper Bulb w/ Union200 - 260°F15 Feet8
PTU-14-15Copper Bulb w/ Union100 - 160°F15 Feet8
PTU-29-15Copper Bulb w/ Union120 - 180°F15 Feet8
PTU-30-15Copper Bulb w/ Union160 - 220°F15 Feet8
PTU-32-15Copper Bulb w/ Union240 - 300°F15 Feet8
Product Overview
PTU Bulb Type is Copper sensing bulb with Union connection allowing it to be screwed into the side of a tank or pipe. The sensing bulb is in direct contact with the process fluid. Sensing bulb can be removed by unscrewing union nut (union hub remains in place).

The PT-Temperature Pilots are used with the HD regulator to control temperature in various processes and systems. Some examples are: oil heaters, ovens, process heaters, vats, dryers and jacketed kettles. Thermostatic sensing bulb comes with standard 8-ft. or 15-ft. capillary lengths. Temperature adjustment is accomplished by rotating an adjustment knob to the desired temperature setting.

The HD Regulator can be used with both the PP-Pressure Pilot and PT-Temperature Pilot simultaneously to limit pressure and control temperature in process applications.
Features
• Temperature adjustment made simple and easy by rotating an adjustment knob to the desired temperature setting
• Thermostatic sensing bulb comes with an 8-ft. or 15-ft. length capillary
• Capillary is armor-protected to resist damage
• Overheat protection bellows is incorporated into sensing bulb; 200°F overheat protection up to 350°F
• Full port strainer and blowdown valve on pilot adapter for protection of pilot from dirt and scale
How It Works
Controlling Temperature
PT-pilot is used for temperature control when steam is used on heating applications. The PT style pilot is a “solid liquid fill” design made up of a temperature probe connected by a length of capillary tubing to a bellows in the pilot valve. When the temperature bulb is heated the liquid inside the probe expands the bellows and closes off the pilot valve. The opening and closing of the pilot controls the flow of steam thru the main valve; which maintains system temperature. PT-pilot controls temperature through a range of 60-300°F. An overheat protection bellows is incorporated into sensing bulb.



Controlling Temperature & Limiting Pressure to a Maximum Value
The PT & PP Pilots combination is used when it’s required to control temperature while limiting downstream pressure to a maximum value. When the PT & PP Pilots combination is used, the downstream pressure is limited to a maximum setting by the pressure pilot, while the temperature pilot maintains the correct temperature of the process. This eliminates the need for a separate pressure reducing valve.

Selection / Sizing / Capacities
Example Model Code:
PTU-29-8 is Copper sensing bulb with Union connection, 120 - 180 °F with standard 8 ft capillary Length). If  it is changed to 20 ft of capillary. Model code becomes PTU-29-20.

Use Code LP:

Low pressure Temperature Pilot is required for steam pressure under 15 PSI. (Range 5 - 20)

Use Code SSBBAC:

The standard sensing bulb is copper. A 316 SS Bulb and bushing with 8 ft. armoured capillary is available for corrosive applications or to meet SWDA requirements. Use code SSBBAC.
Dimension and Weights