Products
Main Image
 
  • HSP-400x400
  • HSP-A-400x400
  • HSP-B-400x400
Technical Specification
  
Size1 1/2"
Connection150# FLG
Max. Operating Pressure (psig)450
Max. Operating Temperature650°F
Max. Allowable Pressure (psig)550 PSIG @ 650°F
Max. Allowable Temperature650°F @ 550 PSIG
Inlet Pressure Range5 - 20
Minimum Differential Pressure3 PSIG
Material Specification
  
BodySS,A351 GR CF8M
CoverSS,A351 GR CF8M
Diaphragm CoverSS,A351 GR CF8M
PilotSS,A351 GR CF8M
GasketGarlock 3400/grafoil SLS
Seat420F Stainless Steel
Disc420F Stainless Steel
DiaphragmBronze
Diaphragm ChamberEPDM
Mfg. BoltsSA-193,GR B7
Spring302 SS
Stem416SS
HSPR-SS-16-F150-B-LP
QTY :
Product Overview
The HSP  & HSP-SS Series Main Valve with Integral Pressure Pilot reduces steam pressure in steam system piping mains and process applications. This pilot-operated regulator is specifically used in applications where the properties and benefits of Cast Steel or Stainless Steel are desired and/or specified. Using steel as the material of construction for the main valve body extends the pressure-temperature rating of the regulator. A unique two-bolt pilot adapter design and field-reversible tubing offer even greater versatility to this type of regulator, further reducing maintenance downtime. These valves share the same design and proven reliability of the Watson McDaniel HD-Series Regulators, providing extremely accurate control of downstream system pressure even when inlet pressure to the regulator fluctuates or steam usage varies.
Features

• Cast Steel body for higher pressure and temperature ratings
• Stainless Steel body for improved corrosion resistance
• New, convenient bolt-on pilot design simplifies installation
• New diaphragm design improves performance and extends life
• Hardened stainless steel trim for extended life
• Optional Stellite trim available
• Full port strainer and blowdown valve on pilot adapter for ultimate protection from dirt and scale
• Maintains downstream pressure to ±1.0 PSIG
• Choice of three overlapping spring ranges
• Pre-mounted pilot & tubing simplifies installation

Dimension and Weights

Installation and Maintenance

Pilot Mounting
Standard pilot mounting is on the right side of the regulator when looking into the outlet port. For opposite-mounting, specify when ordering. Pilot mounting on HSP & HSP-SS regulators are field-reversible.

Pressure Pilot
The spring-adjusted Pilot is used for general purpose pressure reducing applications.