From the Capacity chart, find the inlet pressure and required regulator outlet pressure. Follow across chart to nearest capacity (steam, air, water) that meets or slightly exceeds demand requirements. Follow vertically up to determine appropriate size. When exact application values are not shown, interpolate between values. Select a model with the spring range that accommodates the required outlet set pressure.
Example:
Application: 30 GPM of 100 PSIG of water reduced to 30 PSIG
Model Code: OHC-13-N-0005-V (3/4” HC O-Series, 30-50 PSIG spring range, NPT for Water)
** 3/4" HC is high-capacity version of standard 3/4" valve.